Maintenance
7-10
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Putting a New Module into Service
Table 7-3 Putting new modules into service
Step Putting a Module into Service
1. Open the front door.
2. Bring the front connector back into its operating position.
3
2
ET0057
3. Close the front door.
4. Switch on the power supply for the IM 153-x.
5. Switch the load voltage back on.
Response of the ET 200M After Module Replacement
When you have replaced a module and no errors have occurred, the IM 153-x
starts data transfer. If the IM 153-x stays in STOP mode, you can display the
cause of the error with STEP 5 or STEP 7