SED2 Operation & Maintenance Manual
42 Siemens Building Technologies, Inc.
Index:
P0756[0]: IN000=Analog input 1.
P0756[1]: IN001=Analog input 2.
Note on dependency:
This function is disabled if the analog scaling block is programmed for negative output setpoints
(see P0757 to P0760).
Note on the monitoring function:
If monitoring is enabled and the deadband is defined (P0761), a fault message appears (F0080)
as soon as the analog input voltage drops below 50% of the deadband voltage.
P0753, Analog input filter time
P0753 defines the filter time (PT filter time) in ms for the analog input.
Setting range: 0 to 10,000 ms
Factory setting: 100 ms
Index:
P0753[0]: IN000=Analog input 1.
P0753[1]: IN001=Analog input 2.
Increasing this time reduces (smoothes) the ripples, but also slows down the response to the
analog input.
P0757 – P0760, Input scaling for analog inputs
Parameters P0757 to P0760 configure the input scaling for
the analog inputs according to the following curve.
Factory setting: 0V = 0% and 10V = 100%.
Setting range Parameter
Unit Point on
x/y-axis
Min. Max.
Factory
Setting
P0757 V or mA x1 value -50.0 150.0 0
P0758 % y1 value -99999.9 99999.9 0.0
P0759 V or mA x2 value -50.0 150.0 10
P0760 % y2 value -99999.9 -99999.9 100.0
ymax
y2
(P0760)
y1
(P0758)
x1
(P0757)
x2
(P0759)
%
V
mA
ymin
10
20
-10
-20
NOTE: Use r0752[0] or [1] to read the actual current or voltage.
Use r0754[0] or [1] to read the current or voltage after scaling.
Index: Example for P0757, applies also to parameters P0758 through P0760.
P0757[0]: IN000=Analog input 1.
P0757[1]: IN001=Analog input 2.
Signal in %
Time in ms