SED2 VFD Electronic Bypass Option Operating Instructions
Electrical Installation
See Figure 6 for all Electronic Bypass Option wiring.
1. Route shielded twisted pair (recommended wire type) cable, 24 gauge minimum control
wiring in conduit through knockout and into housing (Figures 7 through 9). Connect control
wiring per job-specific drawings.
NOTES:
Terminate shield at control device.
Control wiring is 12 to 26 AWG and tightening torque is 5 lb-in.
2. If applicable, route communications wiring (P1) in conduit through knockout and into housing
(Figures 7 through 9). Continue to route communications wiring to VFD and terminate per
SED2 VFD Operation & Maintenance Manual.
3. Route motor wiring in conduit through knockout and into housing (Figures 7 through 9).
Connect motor wiring to motor overload and ground lug. See Tables 1 through 4 for wire
sizes and tightening torques.
4. Route input power wiring in conduit through knockout and into housing (Figures 7 through 9).
Connect input power wiring to disconnect switch and ground lug or to circuit breaker and
ground lug. See Tables 1 through 4 for wire sizes and tightening torques.
GND
LUG
M1
(5) (6)
(T1)
OL1
1T1
1T2
(T2)
(T3)
1T3
M
(1) (2)
M2
(1) (2)
A2
B2
U
V
(3)
(5) (6)
(4)
C2
W
(3) (4)
2L1
2L2
A1
B1
U1
V1
U
VFD
L1
C1
W1
WL3
GND
L2 V
R
S
B2
A2
2L3
A1
B1
3L1
3L2
T
C2C1
3L3
FU1
1L1
1L2
(L1)
L1
L2
(T1)
DISC1
M3
(2)
(4)
(6)
1L3
(L3)
L3
(T3)
GND
(L2)(T2)
1L1 1L2
(5)
(3)
(1)
OPTIONAL SUPPLEMENTARY
POWER FUSES - MAIN SHORT
CIRCUIT PROTECTION BY OTHERS
(SEE NOTE 1)
OPTIONAL
DRIVE INPUT
CONTACTOR
OPTIONAL
INPUT LINE
REACTOR
OPTIONAL
OUTPUT LOAD
REACTOR
AC MOTOR
(CUSTOMER
SUPPLIED)
GND
LUG
POWER
SUPPLY
3 PHASE
60 Hz
BRANCH CIRCUIT PROTECTION TO BE PROVIDED BY INSTALLER,
PER UL508A, IF NOT PROVIDED WITH DRIVE.
FOR BYPASS OPERATION MODIFY THESE DRIVE PARAMETERS:
P0704(0) & P0704(1) = 3, P0748 = DIGITAL OUT 1 REVERSE ( ).
CONTROL & COMMUNICATION WIRING SHOULD BE 300V UL MINIMUM.
COMMUNICATION WIRING SHOULD BE RUN WITH MAXIMUM SEPARATION
POSSIBLE FROM ALL OTHER WIRING.
ESSENTIAL SERVICE MODE OPERATES THE MOTOR FULL SPEED (BYPASS)
WITH NO PROTECTION FOR THE MOTOR OR SYSTEM.
ENSURE THAT AUTOMATIC BYPASS WILL NOT DAMAGE THE SYSTEM
BEFORE ACTIVATING.
REFER TO SIEMENS PUBLICATION NO. 125-3208 FOR PROPER FUSE
AND WIRE SIZES.
REFER TO SIEMENS PUBLICATION NO. 125-3208 FOR SED2 VFD
INPUT/OUTPUT CONTROL SIGNAL WIRING DETAILS.
1.
2.
3.
4.
5.
6.
7.
8.
NOTES:
TO
STEP-DOWN
CONTROL
TRANSFORMER
VFD0110R1
GND
Figure 6. Electronic Bypass Option Wiring Schematic.