Siemens RDG400 room thermostat N3182en
Building Technologies May 27. 2009
Functions
Room temperature control via built-in temperature sensor or external room
temperature / return air temperature sensor
Automatic or manual changeover between heating and cooling mode
Selection of applications via DIP switches
Selection of operating mode with operating mode button on the thermostat
Display of current room temperature or setpoint in °C and/or °F
Minimum and maximum setpoint limitation
Button lock (automatic or manual)
3 multifunctional inputs, freely selectable for:
Operating mode switchover contact (keycard, window contact, etc.)
Changeover sensor for automatic heating / cooling mode
External room temperature or return air temperature
Dewpoint sensor
Electrical heater enable
Faults
Minimum and maximum limitation of air flow signal DC 0…10 V
Floor heating temperature limit
Reload factory settings for commissioning and control parameters
Applications
The thermostat supports the following applications, which can be configured via DIP
switches at the rear of the unit. The control output for the damper actuator is either
DC 0…10 V (factory setting) or 3-position (see parameter P47), and for the auxiliary
heating / cooling output ON/OFF, PWM, 3-position or DC 0…10 V.
Application
DIP switch
Control output
DC 0…10 V
Single-duct
DC 0…10 V damper actuator
3-position damper actuator
YV
T
B1
M
V
1 2 3 4 5
ON
OFF
3-position
DC 0…10 V
Single-duct with auxiliary heater
DC 0…10 V damper actuator and
ON/OFF, PWM or 3-position auxiliary
heater
3-position damper actuator and
DC 0…10 V
auxiliary heater
YV
YE
M
V
T
B1
1 2 3 4 5
ON
OFF
ON/OFF, PWM or 3-position
DC 0…10 V
Single-duct and radiator / floor heating
DC 0…10 V damper actuator and
ON/OFF, PWM or 3-position radiator
3-position damper actuator and
DC 0…10 V
radiator
YR
YV
T
B1
1 2 3 4 5
ON
OFF
ON/OFF, PWM or 3-position
DC 0…10 V
Single-duct heating and cooling coil
DC 0…10 V damper actuator and
ON/OFF, PWM or 3-position heating and
cooling
3-position damper actuator and
DC 0…10 V
heating and cooling
YV
M
V
Y1
T
B2
T
B1
1 2 3 4 5
ON
OFF
ON/OFF, PWM or 3-position