Technical and mechanical design
Functio
n The heating element with its solid expansion material converts the electrical positioning
signal to linear
travel of the valve stem. This causes the stem to extend or retract,
opening or closing the valve, depending on the type of valve.
The STS61.. actuator has no rotating parts, ensuring noiseless and wear- and tear-free
operation.
Depending on the connection of the positioning signal (Y or Y), the actuator offers 2
directions of action. It is therefore suited for both NO radiator valves, VD1..CLC small
valves, MiniCombiValves, Combi valves and NC small valves, for example V..P47..
Operation Breakdown
Direction
of action
Positioning signal
DC 0…10 V
Actuator
stem
Valve
behavior
Actuator without operating
voltage
Y increasing Retracted NO opens NO radiator valve, VD1..CLC
small valve, MCV or Combi
valves closed
Y increasing Extended NC opens NC small valve fully open
Direction of action Direction of action
Positioning signal Y increasing
DC 0…10 V
Positioning signal Y increasing
DC 0…10 V
Y
10 V0 V
0 %
100 %
4880Z16
Y
H
Y
10 V0 V
100 %
0 %
4880Z17
Y
H
4880Z18
0 V
4880Z19
10 V
4880Z20
0 V
4880Z21
10 V
Actuator stem retracted
NO (Normally Open)
radiator or Combi valve opens
Actuator stem extended
NC (Normally Closed)
small valve opens
Operation
Breakdow
n When there is no positioning signal DC 0…10 V and a power failure (AC 24 V missing),
the actuator stem is alw
ays extended.
4880Z26
DC 0...10 V
AC 24 V
4880Z27
DC 0...10 V
AC 24 V
NO radiator, Combi valve
The valve is closed.
NC small valve
The small valve is opened.
When the actuator is de-energized, small valve types V..P47.. are fully opened.
Warning
3/8
Siemens Electrothermal actuators CE1N4880en
Building Technologies 11.10.2011