Page 1 - Model FS-250

P/N 315-049353-6 (10.12.05) 8th Edition Siemens Building Technologies Fire Safety FireSeeker Fire Alarm Control Panel Model

Page 2

10 REGULATORY STANDARDS The FS-250 control panel meets the requirements of industry and government regulatory agencies as noted. Federal Communicatio

Page 3 - TABLE OF CONTENTS

14 CONTROL PANEL OPERATION OPERATION INSTRUCTIONS Standby Condition In normal standby operation, the green AC POWER ON LED should be illuminated and

Page 4

15 If the initiating device and the panel are reset before the PAS timer times out, the alarm sequence is aborted. During the investigation period, a

Page 5

16 Abort Function Input modules may be assigned to the “Abort” function. The abort type is selected when programming the releasing group. Failure of

Page 6

17 Supervisory Conditions In case of a supervisory condition, the system supervisory LED activates (ON – flashing) and the sounder activates (ON – pu

Page 7 - INTRODUCTION

18 ADDITIONAL OPERATING PROCEDURES In addition to the basic fire alarm instructions above, several features are included to facilitate maintenance an

Page 8 - PREFACE

19 History The last 2000 system events are time-tagged and recorded for review in the user level event history. This history is available to anyone w

Page 9 - GENERAL DESIGN FEATURES

20 FS-250 OPERATING INSTRUCTIONS Alarm Operation In case of alarm, the Alarm LED flashes, LCD displays alarm condition and the panel buzzer sounds s

Page 10 - REGULATORY STANDARDS

21 FS-RD2 OPERATING INSTRUCTIONS Alarm Operation In case of alarm, the Alarm LED flashes, LCD displays alarm condition and the buzzer activates on-

Page 11 - CONTROL PANEL OPERATION

22 FS-250 WITH RELEASING OPERATING INSTRUCTIONS Pre-Alarm Operation In case of an alarm on one of the devices on a releasing zone, the Pre-Alarm LED

Page 13

45 MAINTENANCE GENERAL The FS-250 provides a maintenance mode to allow for the setting and controlling of various features in the system. The mainte

Page 14

46 QUICK TEST If the control unit has remote connections to the Fire Department or other monitor, be sure to disable the remote signals and notify

Page 15

63 APPENDIX-C: TROUBLESHOOTING DEFINITIONS FOR EVENT HISTORY ENTRIES A. General ENTRY INDICATES ALARM General alarm ALRM Alarm AVCntr Alarm Verify

Page 16

64 B. System Troubles ENTRY INDICATES AC Trouble AC input low or off AddrLp 1 DBLSHT Double short trouble on addressable loop 1 AddrLp 1 OPEN Open

Page 17

65 C. System Events ENTRY INDICATES/NOTES Alarm Silenced MAIN, LCDxx shown on bottom line All AV Ctrs Clr All AV counters cleared AutoProgram Run

Page 18 - Normal Standby Condition

67 APPENDIX-E: ALARM VERIFICATION Alarm verification provides FS-250 with a way to verify an alarm from area type addressable smoke detectors connect

Page 19 - Pre-Alarm Operation

68 APPENDIX-F: APPLICATION SPECIFIC DETECTION Application Specific Detection (ASD) allows the system designer to program an HFP-11 detector’s sensit

Page 20 - MAINTENANCE

69 APPENDIX-G: TESTING/MAINTENANCE If the system is connected to the fire department, etc., or actuates an internal system, disarm the appropriate ou

Page 21 - QUICK TEST

70 APPENDIX-H: LCD, CONTROLS AND INDICATORS The FS-250 has a sounder, 6 LEDs, 4 navigational push buttons adjacent to the LCD display (M1-M4), 3 dedi

Page 22 - APPENDIX-C: TROUBLESHOOTING

71 The sounder operates as follows: SOUNDER Normally OFF – indicates that the system is in supervisory mode or all events in the system have been ac

Page 23 - B. System Troubles

i TABLE OF CONTENTS INTRODUCTION ...

Page 24 - C. System Events

72 The events are displayed one at a time and cycle through a circular list once the first event or last event message is reached.

Page 25

73 APPENDIX-I: GLOSSARY Alarm Signal. A signal indicating an emergency requiring immediate action, such as an alarm for fire from a manual station,

Page 26 - DETECTION

74 Ground Fault. A trouble condition in which a low resistance has been detected between the system wiring and conduit ground. Initiating Device. A m

Page 28 - INDICATORS

Siemens Building Technologies, Inc. P/N 315-049353-6 (10.12.05) 8 Fernwood Road Florham Park, New Jersey 07932

Page 29 - Monday 07/26/04

iiCONTROL PANEL OPERATION ...

Page 30

iii Primary And Secondary Power Wiring ...

Page 32

1 INTRODUCTION CONTROL PANEL LIMITATIONS This control panel may not show an alarm condition without compatible initiating devices (smoke detectors,

Page 33

2 PREFACE Along with the use of this instruction manual, the appropriate following standards and the manufacturer's instructions for initiating

Page 34 - 8 Fernwood Road

9 GENERAL DESIGN FEATURES Environmental The FS-250 panels and its subassemblies are suitable for use in a dry, interior or protected location. Power