Siemens CM300/3 User Manual Page 29

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 28
4. Clear Text Display Module & System Parameters English
© STÖBER plc 1997
27
05.02.01
Parameter Function Range
[Default]
Description / Notes
P910
Local/Remote mode 0 - 4
[0]
Sets the inverter for local control or remote control over the serial link:
0 = Local control
1 = Remote control (and setting of parameter values)
2 = Local control (but remote control of frequency)
3 = Remote control (but local control of frequency)
4 = Local control (but remote read and write access to
parameters and facility to reset trips)
Note: When operating the inverter via remote control (P910 = 1
or 3), the analogue input remains active when P006 = 1
and is added to the setpoint.
P918
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details. (Access only possible with P099 = 1.)
P922
Software version 0.00 -
99.99
[-]
Contains the software version number and cannot be changed.
P923
Equipment system number 0 - 255
[0]
You can use this parameter to allocate a unique reference number to
the inverter. It has no operational effect.
P927
P928
P930
Most recent fault code 0 - 9999
[-]
The last recorded fault code (see section 5) is stored in this
parameter. It is cleared when the inverter is reset.
P931
Most recent warning type 0 - 9999
[-]
The last recorded warning is stored in this parameter until power is
removed from the inverter:
002 = Current limit active
003 = Voltage limit active
005 = Inverter over temperature (internal PTC)
P944
Reset to factory default settings 0 - 1
[0]
Set to ‘1’ and then press P to reset all parameters except P101 to the
factory default settings.
P947
P958
P963
P967
P968
P970
P971
EEPROM storage control 0 - 1
[1]
0 = Changes to parameter settings (including P971) are lost when
power is removed.
1 = Changes to parameter settings are retained during periods
when power is removed.
IMPORTANT
Take care not to exceed the EEPROM write cycle limit of
50,000/parameter (approx.) when using the serial link to update
parameters, otherwise data loss or corruption may occur. Read cycles
are unlimited.
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details. (Access only possible with P099 = 1.)
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details. (Cannot be accessed unless P099 = 1.)
Page view 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 39 40

Comments to this Manuals

No comments