Technical data
Controller and PSU
SPC6330.310-L1
Intrusion CP, G3
SPCP332.300/333.300
Smart PSU
with I/O-Expander
SPCP432.300/433.300
Smart PSU with
2-Door Expander
Number of on-board zones 8, freely programmable
8, freely
programmable
4, for door control
EOL resistor Dual 4K7 (default), other resistor combinations configurable
Dual 4K7 (default), other resistor combinations
configurable
Max. number of hardwired zones 512
Max. number of wireless zones
1)
120
Number of on-board open coll.
2, for internal / external bell (max. 400 mA each)
3, freely programmable
(max. 400 mA each, supplied via auxiliary output)
2, freely
programmable
2, for door control
Number of on-board relays 1, for strobe (single-pole changeover, 30 V / max. 1 A)
(single-pole changeover, 30 V DC / max. 1 A)
Max. number of outputs 512
Programmable areas 60
Max. number of user codes 512
Intrusion Event Logs 10’000 log events shared across all areas
Access Event Logs 10’000 log events
Field bus
2)
X-BUS on RS-485 (307 kb/s) X-BUS on RS-485 (307 kb/s)
Number of field devices
3)
128 (32 Keypads, 32 Door-expanders,
64 Input/Output expanders)
Tamper contact
On-board front cabinet spring tamper
+ 2 auxiliary tamper inputs (back tamper with SPCY130 option)
Front cabinet spring tamper /
back tamper (SPCP333/433)
2 X-BUS (2 spurs or 1 loop)
2 RS232 (RJ45 ports, for X-10 or external communication)
1 USB (PC for browser programming / terminal program)
1 Fast Programmer
Interfaces
1 Ethernet (RJ45)
2 card readers,
Wiegand 26 bits
(standard),
Clock&Data and
Wiegand 36 bit
(proprietary)
Power supply Type A (per EN50131-1), Integrated on controller PCB Type A (per EN50131-1)
Input voltage 230 V AC, +10 to -15 %, 50 Hz at transformer 230 V AC, +10 to -15 %, 50 Hz at transformer
Operating current Controller only max. 200 mA
Max. 95 mA
(all relays activated)
Quiescent current Controller only max. 170 mA Min. 77 mA
Auxiliary power (nominal)
Max. 750 mA
(subject to size of battery fitted & Security Grade required)
Max. 2 x 750 mA (subject to size of battery fitted
& Security Grade required)
Output voltage
11-14 V DC in normal conditions
(mains powered and fully charged battery)
4)
11-14 V DC in normal conditions
(mains powered and fully charged battery)
4)
Battery capacity (Recommended
YUASA battery, not included)
Max. 17 Ah / 12 V
Max. 7 Ah / 12 V (SPCP332/432)
Max. 17 Ah / 12 V (SPCP333/433)
Hinged metal enclosure
Small metal enclosure (SPCP332/432)
Hinged metal enclosure (SPCP333/433)
Housing
1.4 mm mild steel 1.4 mm mild steel
Dimensions (W x H x D in mm) 326 x 415 x 114
264 x 357 x 81 (SPCP332/432)
326 x 415 x 114 (SPCP333/433)
Weight 7.30 kg
5.20 kg (SPCP332/432)
7.40 kg (SPCP333/433)
Colour RAL 9003 (signal white) RAL 9003 (signal white)
Operating temperature -10 to +50 °C -10 to +50 °C
Relative humidity Max. 90 % (non-condensing) Max. 90 % (non-condensing)
Standards
Certified according to
EN50131-1:2006 (Grade 3, Class II Indoor General),
TS50131-3:2003, EN50131-6:2008
1)
A wireless zone takes away a wired zone / optional RF receivers required.
2)
More I/O expanders can be addressed instead of a keypad or door expander, but number of programmable inputs / outputs cannot exceed specified system limits.
3)
Max. 400 m between devices in chain configuration / cable types IYSTY 2 x 2 x Ø 0.6 mm (min.), UTP cat5 (solid core) or Belden 9829.
4)
When the secondary device is powering the auxiliary output, voltages as low 9.5 V can be seen on this output before the system shuts down to deep discharge protection.