Loop Raw Setpoint LSPR<address> 1-65536 Word Read/Write
Loop Raw Error LERRR<address> 1-65536 Word Read Only
Loop Raw High-High Alarm
Limit
LHHAR<address> 1-65536 Word Read/Write
Loop Raw Low-Low Alarm
Limit
LLLAR<address> 1-65536 Word Read/Write
Loop Raw Alarm Deadband LADBR<address> 1-65536 Word Read/Write
Loop Raw Bias LMXR<address> 1-65536 Word Read/Write
Loop Raw Setpoint Low
Limit
LSPLR<address> 1-65536 Word Read/Write
Loop Raw Setpoint High
Limit
LSPHR<address> 1-65536 Word Read/Write
Loop C Flags - MSW LCFH<address> 1-65536 Word Read/Write
Loop C Flags - LSW LCFL<address> 1-65536 Word Read/Write
Loop Derivative Gain Limit
Coef.
LKD<address> 1-65535 Float Read/Write
Loop Ramp/Soak Step
Number
LRSN<address> 1-65536 Word Read/Write
Loop Alarm ACK Flags LACK<address> 1-65536 Word Read Only
*For more information, refer to LVF Bit Definitions.
**For more information, refer to LCF Bit Definitions.
***For more information, refer to LRSF Bit Definitions.
Array Support
Non-Boolean addresses accept array notation. To view data as an array, append '[rows][cols]' to an address. For
example, V500 [2][2], V100 [12].
Packed Task Code Protocol
The following address types and arrays are not supported under Packed Task Code Protocol. CAMP Protocol will be
used instead.
Loop Control (C) Flags (LCF)
Loop Raw High Alarm Limit (LHAR)
Loop Raw Low Alarm Limit (LLAR)
Loop Raw Process Variable (LPVR)
Loop Raw Orange Deviation (LODAR)
Loop Raw Yellow Deviation (LYDAR)
Loop Raw Output (LMNR)
Loop Raw Setpoint (LSPR)
Loop Raw Error (LERRR)
Loop Raw High-High Alarm Limit (LHHAR)
Loop Raw Low-Low Alarm Limit (LLLAR)
Loop Raw Alarm Deadband (LADBR)
Loop Raw Bias (LMXR)
Loop Raw Setpoint Low Limit (LSPLR)
Loop Raw Setpoint High Limit (LSPHR)
LVF Bit Definitions
Loop Variable Flag Data Element Format
The server default settings are shown in bold.
MSB LSB
ABCD EFGH IJKL MNOP
The LVF bit has the following format:
V/W, X/Y
V=0-based bit addressing. Bit 0 is MSB.
W=1-based bit addressing. Bit 1 is MSB (Simatic 505 documentation).
X=0-based bit addressing. Bit 0 is LSB.
Y=1-based bit addressing. Bit 1 is LSB.